Registers
Cable Schedule
CSThe cable schedule is what the installation contractor works from and what the commissioning engineer uses when a signal is missing. It pairs with the I/O list: the I/O list says which signal, the cable schedule says which physical wire carries it.
Do you need this one?
Any installation with field wiring. On a self-contained machine with a wiring loom it can be folded into the panel drawings.
What is in it
- 01Cable identity and type
- 02From and to, with terminal detail
- 03Cores and usage
- 04Route and length
- 05Segregation category
- 06Test results
Written by
Electrical design engineer
Approved by
Client engineering
Written against
- IEC 60204-1 for wiring practice and colour
- IEC 81346 for designation
Preview
Cable Ref,Type,Cores,CSA mm2,Screen,From,From Terminal,From Gland,To,To Terminal,To Gland,Length m,Route,Segregation,Function,Voltage,Continuity Test,Insulation Test,Tested By,Date,Notes C-101,SY,4,1.0,Braid,CP-01,X1:01-04,M20,XV-101,1-4,M16,25,Tray A,Control,24VDC,,,,, C-102,SY,4,1.0,Braid,CP-01,X1:03-06,M20,Local station LS-01,1-4,M16,12,Tray A,Control,24VDC,,,,, C-103,SY,4,1.0,Braid,CP-01,X2:01-04,M20,ESTOP-01,1-4,M16,18,Tray A,Safety,24VDC,,,,, C-104,SY,4,1.0,Braid,CP-01,X2:03-06,M20,GS-101,1-4,M16,22,Tray A,Safety,24VDC,,,,, C-201,Instrument,1 pair,0.5,Foil + drain,CP-01,X3:01-02,M16,FT-101,+/-,M20,30,Tray B,Instrument,4-20mA,,,,,Screen earthed at panel only C-202,Instrument,1 pair,0.5,Foil + drain,CP-01,X3:03-04,M16,LT-101,+/-,M20,28,Tray B,Instrument,4-20mA,,,,,Screen earthed at panel only C-203,Instrument,1 triple,0.5,Foil + drain,CP-01,X4:01-03,M16,TT-101,1-3,M20,35,Tray B,Instrument,RTD,,,,,Three wire RTD C-301,SY,4,1.5,Braid,CP-01,X5:01-04,M20,MCC starter,,M20,45,Tray C,Control,24VDC,,,,, C-302,SY,3,1.0,Braid,CP-01,X5:02-04,M20,XV-101-SOL,1-3,M16,25,Tray A,Control,24VDC,,,,, C-303,SY,3,1.0,Braid,CP-01,X5:03-05,M20,LMP-FAULT,1-3,M16,15,Tray A,Control,24VDC,,,,, C-401,Instrument,1 pair,0.5,Foil + drain,CP-01,X6:01-02,M16,FCV-101,+/-,M20,32,Tray B,Instrument,4-20mA,,,,, C-501,SF/UTP Cat6,4 pair,,Foil,CP-01,SW1 P1,M20,Remote panel CP-02,SW2 P1,M20,60,Tray D,Data,Ethernet,,,,, P-001,SWA,4,16,Armour,MCC,,M32,CP-01 Q1,L1 L2 L3 N,M32,55,Tray E,Power,400VAC,,,,, E-001,Earth,1,16,,Earth bar,,M20,CP-01 PE,PE,M20,55,Tray E,Earth,,,,,,