Registers

Cable Schedule

CS

The cable schedule is what the installation contractor works from and what the commissioning engineer uses when a signal is missing. It pairs with the I/O list: the I/O list says which signal, the cable schedule says which physical wire carries it.

Do you need this one?

Any installation with field wiring. On a self-contained machine with a wiring loom it can be folded into the panel drawings.

What is in it

  1. 01Cable identity and type
  2. 02From and to, with terminal detail
  3. 03Cores and usage
  4. 04Route and length
  5. 05Segregation category
  6. 06Test results

Written by

Electrical design engineer

Approved by

Client engineering

Written against

  • IEC 60204-1 for wiring practice and colour
  • IEC 81346 for designation

Preview

Cable-Schedule.csv
Cable Ref,Type,Cores,CSA mm2,Screen,From,From Terminal,From Gland,To,To Terminal,To Gland,Length m,Route,Segregation,Function,Voltage,Continuity Test,Insulation Test,Tested By,Date,Notes
C-101,SY,4,1.0,Braid,CP-01,X1:01-04,M20,XV-101,1-4,M16,25,Tray A,Control,24VDC,,,,,
C-102,SY,4,1.0,Braid,CP-01,X1:03-06,M20,Local station LS-01,1-4,M16,12,Tray A,Control,24VDC,,,,,
C-103,SY,4,1.0,Braid,CP-01,X2:01-04,M20,ESTOP-01,1-4,M16,18,Tray A,Safety,24VDC,,,,,
C-104,SY,4,1.0,Braid,CP-01,X2:03-06,M20,GS-101,1-4,M16,22,Tray A,Safety,24VDC,,,,,
C-201,Instrument,1 pair,0.5,Foil + drain,CP-01,X3:01-02,M16,FT-101,+/-,M20,30,Tray B,Instrument,4-20mA,,,,,Screen earthed at panel only
C-202,Instrument,1 pair,0.5,Foil + drain,CP-01,X3:03-04,M16,LT-101,+/-,M20,28,Tray B,Instrument,4-20mA,,,,,Screen earthed at panel only
C-203,Instrument,1 triple,0.5,Foil + drain,CP-01,X4:01-03,M16,TT-101,1-3,M20,35,Tray B,Instrument,RTD,,,,,Three wire RTD
C-301,SY,4,1.5,Braid,CP-01,X5:01-04,M20,MCC starter,,M20,45,Tray C,Control,24VDC,,,,,
C-302,SY,3,1.0,Braid,CP-01,X5:02-04,M20,XV-101-SOL,1-3,M16,25,Tray A,Control,24VDC,,,,,
C-303,SY,3,1.0,Braid,CP-01,X5:03-05,M20,LMP-FAULT,1-3,M16,15,Tray A,Control,24VDC,,,,,
C-401,Instrument,1 pair,0.5,Foil + drain,CP-01,X6:01-02,M16,FCV-101,+/-,M20,32,Tray B,Instrument,4-20mA,,,,,
C-501,SF/UTP Cat6,4 pair,,Foil,CP-01,SW1 P1,M20,Remote panel CP-02,SW2 P1,M20,60,Tray D,Data,Ethernet,,,,,
P-001,SWA,4,16,Armour,MCC,,M32,CP-01 Q1,L1 L2 L3 N,M32,55,Tray E,Power,400VAC,,,,,
E-001,Earth,1,16,,Earth bar,,M20,CP-01 PE,PE,M20,55,Tray E,Earth,,,,,,